Code: U2๐Ÿ”ง Daikin Mini Split

Daikin Error Code U2: Power Supply Voltage Problem (Meaning, Causes, Fixes)

Reviewed 2026-10-24 ยท Based on 6 manufacturer & service sources

What the code means

Daikin's service manuals call U2 "Abnormal Power Supply Voltage" (Sky Air and split manuals ESIE05-03 and ESIE13-02) or "Power Supply Insufficient or Instantaneous Abnormality" (VRV manual SiME341909EA). The outdoor unit watches the voltage of the main circuit capacitor inside the inverter along with the incoming supply voltage, and sets U2 when that voltage drops below its range or the power cuts out for even a fraction of a second. The exact limits depend on the model: ESIE13-02 gives about 150-170 VAC (or DC outside 305-380 VDC) for single-phase V3 units, and the VRV manual uses a DC circuit voltage below 380 VDC. Newer R32 Sky Air units (ESIE17-08) show it as U2-00 and also trigger it on an abnormal voltage rise or when the indoor board sees no zero-cross signal for about 10 seconds. Daikin's simple self-diagnosis chart sums U2 up as a malfunction of power supply or instantaneous power failure. It points at the electrical supply first, not at refrigerant.

Likely causes

Safe DIY checks

โš  Before you start

Turn off the breakers for both the indoor and outdoor units before any inspection. Daikin's manuals warn to turn off the power switch before connecting or disconnecting connectors, or parts may be damaged. The outdoor inverter board holds main circuit capacitors at several hundred volts DC that can stay charged after power is off, so leave voltage measurements and board work to a licensed electrician or HVAC technician.

  1. Think about what just happened. If U2 appeared right after a storm, a power flicker or a breaker trip, a momentary power failure is the listed cause and a reset often clears it.
  2. Do a full power reset: switch off the breakers or disconnect for the outdoor and indoor units, wait a few minutes, then switch them back on. Daikin's R32 Sky Air manual resets U2 by power-resetting the outdoor unit, and notes the indoor unit may need a power reset too.
  3. After the reset, give it a few minutes. Daikin's manual notes the compressor restarts on its own after a 3-minute standby when the voltage returns to normal.
  4. Notice whether lights dim or other equipment struggles when the system starts. That points at low household or utility voltage rather than the unit itself.
  5. Avoid running other heavy loads on the same circuit, and check that the breaker feeding the outdoor unit isn't warm, buzzing or tripping.
  6. Don't open the outdoor unit or the disconnect to measure voltage yourself. The inverter capacitors carry high DC voltage that can stay charged after the power is off.

๐Ÿ›  When to call a pro

  • U2 returns after a full power reset. An electrician or HVAC technician measures the supply voltage at the outdoor unit, which is Daikin's first check, along with open phases and wrong wiring.
  • The supply voltage sags or is unbalanced. Daikin's remedy is to fix the power supply first; on three-phase systems the VRV manual wants 380-415 V and imbalance within 12 V.
  • The supply checks out. The technician inspects the main circuit wiring, then tests the outdoor or inverter board, which Daikin says to replace when its DC voltage or over-voltage detection circuit is faulty.
  • On VRV systems, the technician checks compressor insulation resistance, since Daikin's flow replaces the compressor when it reads 100 kฮฉ or less.
  • Newer models still show U2 after those checks. Daikin's manuals go on to the outdoor fan motor, the indoor unit board and the indoor/outdoor wiring before contacting the helpdesk.
  • The code follows utility problems in your area. Ask the power company to check the voltage at your meter, since a utility-side issue can't be fixed at the unit.

Parts that commonly fix it

Always match the part number to your exact model.

โš™

Outdoor unit inverter control board

Replaced when Daikin's diagnosis points at the inverter or main PCB; match the exact outdoor model number before ordering.

Search eBay โ†’
โš™

Multimeter

Used by the technician to check supply voltage and phase balance at the outdoor unit.

Search eBay โ†’
โš™

Main circuit wiring and connections

Loose or burned supply connections are a listed U2 cause; a technician should match wire size to the installation manual.

Search eBay โ†’

Sources

  1. Daikin service manual ESIE13-02, p.141 "U2" Abnormal Power Supply Voltage: detection, decision conditions (V3 150-170 VAC or DC outside 305-380 VDC) and supposed causes, via ManualsLib
  2. Daikin service manual ESIE05-03 (Sky Air RZQ), 3.23 Abnormal Power Supply Voltage (U2): drop to 180 V or less, instantaneous power failure, inverter open phase, wiring, outdoor PCB, via mcgrp.ru
  3. Daikin service manual SiME341909EA (VRV X), 5.51 Power Supply Insufficient or Instantaneous Abnormality U2: DC circuit below 380 VDC, supposed causes and troubleshooting flow, via EasyManuals
  4. Daikin service manual ESIE17-08 (R32 Sky Air RZAG-M), U2-00 Power supply abnormality or instantaneous power failure: triggers, 3-minute restart, checks, via mans.io
  5. Daikin service manual ESIE18-01 (RXP-L2V1B), U2-00 checks: power supply, compressor, outdoor fan motor, main PCB, indoor PCB, power reset via outdoor unit (Daikin UK tech site)
  6. Daikin Industries, Simple Self-Diagnosis by Malfunction Code (U2 malfunction of power supply or instantaneous power failure: abnormal supply voltage, instantaneous power failure, defective main circuit wiring)

Last reviewed 2026-10-24. Always confirm against the manual for your exact model number.