American Standard / Trane Error 67.06: Suction Temperature Sensor Fault in Cooling (Meaning, Causes, Fixes)
What the code means
American Standard and Trane are sister brands, and their communicating systems share one alert list. The 67 family covers the outdoor unit's temperature sensors: 67.00 ambient, 67.01 coil, 67.02 liquid line, 67.03 external outdoor sensor, 67.04 and 67.05 compressor dome (cooling and heating), 67.06 and 67.07 suction temperature (cooling and heating), and 67.08 compressor dome sensor not attached. Trane's System Alert Guide (August 2020) describes ERR.067.06 SUCTION TEMPERATURE SENSOR FAULT COOLING as: suction temperature sensor is faulted in cooling mode. The ComfortLink II alert table lists it as CL2.067.06, SUCT T SENSE, Major. The suction sensor sits on the suction (larger, insulated) refrigerant line at the outdoor unit, and the control uses it, together with pressure readings, to work out superheat. Trane's guide notes that on outdoor software version 3.x and later, a faulted suction temperature sensor can put the system into limp mode in heating (175.00, compressor speed fixed to a constant value); the guide lists that for heating only, so in cooling expect the 67.06 alert itself. 67.07 is the same fault seen in heating mode.
Likely causes
- The suction temperature sensor is open or shorted. Trane's check is a resistance reading: zero or infinite resistance means the sensor or its leads have failed.
- The sensor reads out of range. Trane says to compare its resistance to the temperature/resistance chart in the unit's literature; a sensor that's drifted, loose on the pipe, or poorly insulated can read wrong.
- No output voltage from the control board to the sensor. Trane's guide says a reading between 3 and 5 VDC at the board with the sensor removed confirms good source voltage; the ComfortLink II table says 5 VDC should be measured with the sensor disconnected.
- Damaged or unplugged sensor wiring between the sensor and the outdoor control board, for example from rodents, string trimmers or a connector that worked loose. This follows from Trane's open-circuit and no-voltage checks rather than being a separately listed cause.
Safe DIY checks
Turn off power at the furnace/HVAC service switch and the breaker before opening panels.
- Note whether the alert shows as current or only in history, and whether it says cooling (67.06) or heating (67.07). Write down any other alerts from the same time, such as other 67.xx sensor alerts or 175.00 limp mode.
- Turn the system off at the thermostat, wait a few minutes and turn it back on. If the alert returns right away, the sensor or its wiring is the likely problem.
- With power off at the outdoor disconnect, look along the insulated suction line near the outdoor unit for chewed, cut or crushed sensor wires or insulation that's been pulled away. Don't open the unit's control panel.
- Keep the area around the outdoor unit clear so a technician can reach the service panel.
🛠 When to call a pro
- Measuring the sensor's resistance and comparing it to the chart in the outdoor unit's literature at the actual pipe temperature; replacing it if it reads zero, infinite or out of range.
- Checking the source voltage at the control board with the sensor unplugged (Trane gives 3 to 5 VDC in the alert guide and 5 VDC in the ComfortLink II table). No voltage points to the outdoor control board.
- Repairing damaged sensor wiring or a loose connector, and making sure the replacement sensor is clamped to the suction line in the correct spot and insulated.
- If the alert keeps coming back with a good sensor and good voltage, checking the outdoor unit's software version and the related superheat and limp-mode alerts with Trane's service literature.
Parts that commonly fix it
Always match the part number to your exact model.
Suction line temperature sensor
Must match the outdoor unit's model number; Trane says to compare resistance against the chart in that unit's literature.
Search eBay →Digital multimeter
For the resistance and source-voltage checks Trane lists. Work inside the outdoor unit is for someone qualified.
Search eBay →Outdoor control board
Only if the board isn't supplying source voltage to a known-good sensor. Use the board for your exact model.
Search eBay →Sources
- Trane System Alert Guide (Aug 2020), pp. 12-14: ERR.067.00-067.08 outdoor sensor faults, including ERR.067.06 Suction Temperature Sensor Fault Cooling (sensor open or shorted, zero or infinite resistance, out of range, compare to chart, no output voltage, 3-5 VDC with sensor removed); p. 33: ERR.175.00 limp mode from suction sensor fault in heating (distributor-hosted copy)
- Trane ComfortLink II alert codes table: CL2.067.06 Major, SUCT T SENSE, suction temperature sensor faulted in cooling mode, 5 VDC with sensor disconnected (distributor-hosted copy)
Last reviewed 2026-10-25. Always confirm against the manual for your exact model number.